As data centers become more unified and dependent on continuous uptime, monitoring the health of power and cooling systems is essential. Oil Testing and Lubricant Analysis in a preventive maintenance strategy provides early insights into equipment condition, helping prevent failures in generators, UPS systems, chillers, compressors, and pumps. Fluid analysis shifts maintenance from redundancy-based to predictive-based, improving reliability and operational performance.
Atlas Lab offers specialised oil and lubricant testing for data centers, analysing samples as per ASTM, ISO, and IP standards. As a NABL-accredited and ISO 17025-certified laboratory, we evaluate viscosity, oxidation stability, particle count, ferrous density, water content, wear metals, TAN/TBN, and additive depletion. These tests identify contamination, degradation, and early mechanical wear.
With decades of technical expertise and fast reporting, Atlas Lab helps data centers optimise maintenance intervals, reduce downtime, and ensure long-term equipment health. Our solutions provide a cost-effective, data-driven approach to maintaining critical infrastructure.

Power Train
Cooling Train
| Application / Fluid | Recommended Test Slate | Sample Size | Sample Frequency |
|---|---|---|---|
| Diesel Generators (Lube Oil) | Elemental Analysis (21-elements), Viscosity, Fuel Soot, Oxidation, Nitration, Water (%), Glycol, Fuel Dilution, and Total Base Number. | 4 oz / 120 mL | 250-hrs or Semi-Annual |
| Diesel Generators (Antifreeze / Coolant) | Elemental Analysis (Corrosion & Inhibitor Metals), Appearance, Color, Foam, Odor, pH, Glycol %, Freeze Point, Nitrites, and Total Hardness. | 4 oz / 120 mL | 250-hrs or Semi-Annual |
| Turbine Generators (Lube Oil) | Elemental Analysis (21-elements), Viscosity, Total Acid Number, Water (ppm) and ISO Particle Count. | 4 oz / 120 mL | 200-hrs or Quarterly |
| On-Site Fuel Storage (Diesel Fuel) | Particulate Contaminant, Sediment & Water | 16 oz / 500 mL | Annually |
| New Fuel Deliveries (Diesel Fuel) | Distillation, Density, Cetane Index, Sulfur, Flash Point, Copper Corrosion, Cloud Point, Ash, Sediment & Water, Viscosity, Carbon Residue. | 32 oz / 1 L | At Delivery |
| HVAC / CRAC (Refrigeration Oil) | Elemental Analysis (21-elements), *Total Acid Number, and Water (ppm), * Total Base Number |
4 oz / 120 mL | Semi-Annual |
| HVAC / CRAC (Refrigerants) | Water (ppm), Acidity, Sediment, Appearance, and Color | 32 oz. (Steel Canister Required) | Semi-Annual |
| Chillers / Cooling System (Cooling Water / Condensate) |
Elemental Analysis (21-elements), Appearance, pH, Total Hardness, Alkalinity, Total Disolved Solids, Total Suspended Solids, Chloride, Sulphate, Nitrite, Turbidity, Density, Conductivity, % Glycol, Freeze Point | 8 oz / 250 mL | Semi-Annual |
| Chillers / Cooling System (Water-Glycol) |
Elemental Analysis (Corrosion & Inhibitor Metals), Appearance, Color, Foam, Odor, pH, Glycol %, Freeze Point, Nitrites, Total Hardness | 8 oz / 250 mL | Semi-Annual |
| Transformers (Insulating Oils) | Total Acid Number, Color, Visual, Specific Gravity, Moisture Content (Karl Fischer) | 16 oz / 500 mL | Annual |